Power Supply Trouble Codes

Most trouble codes operate the same way for all firmware versions. The trouble codes that operate differently depending on firmware version have a section for each firmware version.

The trouble codes below may be generated by the EST3 power supplies:

Code Message Operation
610
 
Rail Voltage Out of Spec
 
Common
 
611
 
Rail DC Below Battery Voltage
 
Unused
 
612
 
Heat Sink Too Hot
 
Unused
 
613
 
Low Battery Cut Off
 
Common
 
614
 
AC BrownOut
 
See Notes
 
615
 
Battery Trouble
 
Common
 
616
 
Aux Power Ckt 2 Overload
 
Common
 
617
 
Power Supply Fail
 
See Notes
 
618
 
Aux Power Ckt 1 Overload
 
Common
 
619
 
Driver Power Supply Dead
 
Unused
 